ZETA Input Unit - Switch Monitor Module
  • The ZETA Addressable Input Units (ZIU) is used to interface external equipment which has a volt free Normally Open relay output to any Zeta Analogue Addressable fire alarm system. The Input is monitored with a 47K end of line resistor.
  • The Unit has a built in loop short circuit isolator to help keep the unit operational in the event of a problem on the addressable loop wiring.
  • It has 3 indication LEDs on the front of the unit. One of ALARM , One for Local Fault and one for Addressable Loop Fault (Isolator Active)
Price : On Request - In Stock.
 
 
Technical Specifications
Dimensions : 127 x 88 x 59mm
IP Rating : IP43
Operating Temperature : -20° +90°C
Humidity : 95%
Weight : 220g
Electrical Specifications    
Operating Voltage : 17-33V DC
Quiescent Current : 2mA
Alarm Current : 2mA
Isolating Current : 7,3mA
Fault Current : 2,8mA
Device Normal Resistance : 10K to 75K
Device Open Fault Resistance : 85K to Open Circuit
Maximum Rating Continuous 1A
Maximum Taring Switching Current : 3A
Isolation Voltage : 15,6V
Isotaliton Responce Time : 25us to 300us
Reconnection Time : Up to 2 Sec
Reconnection Voltage : 18,5V
End of Line Resistor : 47K