C-TEC C4408DR Relay Base With Diode
Overview
The C-TEC C4408DR Relay Base With Diode is designed for use with C-TEC’s full range of ActiV fire detectors, including smoke, heat and multisensor models. It provides an integrated relay output for general purpose switching applications and is suitable for conventional fire alarm installations where a diode relay base is required.
This base includes a 1A at 24V DC relay controlled by the detector’s remote LED output, allowing it to interface with a wide variety of external systems. It is ideal for switching CCTV, security, SCADA, PLC and door retaining systems, while also offering easy installation, remote LED terminals and compatibility with intruder alarm panels when used as a fire-triggering interface.
Key Features
- Full ActiV compatibility: compatible with C-TEC’s entire range of ActiV fire detectors.
- Integrated relay output: includes a 1A @ 24V DC relay controlled by the detector’s remote LED output.
- Versatile interfacing: ideal for switching CCTV, security, SCADA, PLC and door retaining systems.
- EN54 related compliance: third-party certified to the relevant parts of EN54 in conjunction with ActiV detectors.
- Easy installation: designed with ample working space for straightforward fitting and field wiring.
- 360° visibility support: can be ceiling mounted in any orientation due to the true 360° viewing angle of ActiV detector LED strips.
- Integrated practical features: includes detector/base locking mechanism, head removal tool provision and ID tag.
- Click-and-twist fitting: simple and secure detector mounting design.
- Remote LED provision: terminals available for optional connection to a BF318 remote indicator.
- Alternative version available: C4408R non-diode relay base is also available for systems that do not require head-out monitoring.
Product Highlights
The C4408DR is intended for projects where a conventional fire detector needs to provide an isolated switching output for auxiliary control or system interfacing. Its relay contacts allow the base to be used in a wide variety of integration scenarios, from fire zone interfaces to external automation and monitoring equipment.
It can also be connected in a similar way to a PIR or magnetic door contact on a dedicated fire zone or spare intruder alarm panel zone. When used with a 12V-24V detector, the system can trigger alarm sounders or dedicated fire outputs on compatible panels, making it a practical solution for hybrid fire-security applications.
Technical Specification
| Parameter | Specification |
| Model | C4408DR |
| Description | Relay Base With Diode |
| Compatibility | Compatible with C-TEC’s entire range of ActiV fire detectors |
| Approval / Certification | Certified to the relevant parts of EN54 by Intertek as part of ActiV fire detector certifications |
| Supply Voltage | 9 - 33V DC |
| Wiring | (1) +V In; (2) +V Out; (3) Remote LED +V; (4) 0V; (5) 0V; (6) Screen; (7) Screen. NO/C/NC relay connections. Contact rating at 24V DC is 1A |
| Terminal Capacity | Terminals can accept up to 2.5 mm fire-rated cable |
| Supply / Monitoring Type | 2-wire monitored, polarity sensitive |
| Relay Contacts | NO / C / NC relay connections, 1A @ 24V DC |
| Dimensions | 102.2 mm diameter x 30 mm depth |
| IP Rating | IP42 |
| Weight | 86 g |
For detector compatibility, wiring assistance and project pricing, please contact our sales team.