Sismik Sislift 2 Contact Output Seismic Sensor / Earthquake Sensor
Sismik Sislift 2 Contact Output Earthquake Sensors activate predefined emergency scenarios and allow elevators to stop safely and complete travel to the nearest floor in public and residential buildings such as hospitals, schools, factories, and more.
Sismik Sislift seismic sensors can also be used with power generators, solenoid valves, and power supply systems. The unit provides two dry contact outputs with NO & NC options, enabling control of two different elevator lines or other safety scenarios such as gas shut-off and power cut-off facilities.
Technical Specifications
| Parameter | Value |
|---|---|
| Supply Voltage | 170V - 250VAC 50Hz |
| Standby Current | 30mA |
| Battery Size | 12V 2.2Ah |
| Battery Duration | 24 Hours |
| Battery Check | Auto |
| Working Temperature | 0°C to +51.5°C |
| Installation Angle | Horizontal 0° |
| Discharge Battery Level | 11.85 VDC (±5%) |
| Dimensions | 185mm × 180mm × 90mm |
| Weight | 2.7Kg |
| Dry Contact Outputs | 2 × NO & NC |
Display and Alarm Features
| Feature | Details |
|---|---|
| Earthquake Alarm | Inbuilt Sounder and LED Indicator |
| Main State Indicator | YES |
| Battery State Indicator | YES |
| Battery Fault Monitoring | YES - Battery backup is always checked. If the charge voltage level cannot reach 11.85V, the user will hear an audible notification. |
| Solenoid Valve Line Fault Monitoring | YES - If any short circuit or open circuit fault occurs on the solenoid valve cable, LED indicators and the sounder will be activated to alert users. |
| Auto Battery Charge Function | YES |
| Reset Button | YES |