Approval Certifications: |
Certified to EN54-5 & 7 by Intertek (0359-CPR-00183). |
Application : |
s well as operating independently, the C4414’s smoke & heat sensors combine to produce a sensitive response to freely burning fires, e.g. when a rise in heat is detected, its smoke response level reduces for improved detection and reduced false alarms. |
Application Temperature : |
25°C typical, 50°C max. |
Static Response Temperature : |
54°C min, 65°C max. |
Sensitivity : |
Nominal alarm threshold of 0.16db/m obscuration measured in accordance with EN54-7:2000. |
Supply Wiring : |
2-wire monitored, polarity sensitive. |
Supply Voltage : |
9 - 33V DC |
Quiescent Current : |
30µA @ 24V DC |
Switch on surge current |
120µA @3 saniye |
Alarm Gerilimi : |
6 - 33V DC |
Alarm Current : |
19mA @ 12-33V DC; 11mA @ 9V DC; 2.5mA@ 6V DC |
Min. Gerilim : |
6V DC |
Min. alarm tutma akımı: |
2.5mA |
LED Gösterge İçin Min.Gerilim: |
6V DC min |
Alarm Reset Voltage : |
Less than 1V DC (+0.5 seconds alarm reset time) |
Expansion Connections : |
Remote LED output available via ActiV base. Current source to the negative line, short-circuit protected. Max voltage 2.7V DC |
IP Rating : |
IP42 |
Dimension : |
102.2mm diameter x 37mm deep (detector in base); 102.2mm diameter x 57.5mm deep. |
Weight : |
Detector: 99g. Base: 55g. |
Contruction & Finish : |
White polycarbonate casing rated to UL94 V-2 with nylon parts |