Power Supply Specification |
Mains Supply Voltage : |
220V 50Hz AC |
Internal Power Supply : |
24V Noninal |
Max. Output Current : |
3A @230V AC |
Power Rating (Including Charging) : |
1,5A Cont. , 3A Peak |
Battery Type : |
2 X 12V 7Ah VRLA Tip Akü (Seri Bağlantı) |
Battery Charge Current : |
0,7A |
Earth Fault Monitoring : |
YES |
Mains Supply / Battery Charged Monitorinf for failure : |
YES |
Batteries Monitored for disconnection or failure : |
YES |
Quiescent Current drain on mains Fail: |
40mA |
|
|
Detector Circuit Specification |
No. of Conventional Circuits : |
3 X 21-28V |
Line monitored for open and short circuit : |
VAR |
Max. Cable Lenght Per Circuit : |
250 Metre |
Max. Number of Smoke/Heat Detector Per Circuit : |
20 Adet |
Max. Number of Combine Smoke/Call Point Per Circuit : |
32 Adet |
Zone Quiescent Current : |
2mA Max |
End-Of-Line Resistor Value : |
6K8 ohm ± 5%, 0.25W |
|
|
Sounder Circuit Specification |
|
No. of Conventional Circuit : |
3 (two x 1st stage, one x 2nd stage) |
Line monitored for open and short circuit faults : |
YES |
Sounder outputs rating : |
21-28Vdc, fused @200mA per circuit |
Max. sounder cable length per circuit : |
Her bir devre için 50 Metre |
Max. number of polarised sounders per circuit : |
10 @ 20mA each |
End-of-line resistor value : |
6K8 ohm ± 5%, 0.25W |
|
|
Auxiliary outputs |
|
No. of auxiliary outputs *: |
6 (Fire, Local Fire, Extract Fan, 1st Stage, 2nd Stage, Fault) |
Relay contact rating : |
30Vdc, 1A maks. |
|
|
Extinguishant release outputs |
|
Extinguishant release output |
21-28Vdc, rated at 1A for 5mins |
Extinguishant release time delay |
Adjustable 0-60 seconds (1 second steps) |
Extinguishant release duration |
Adjustable 1-300 seconds (1 second steps) |
Extinguishant release flooding time |
Adjustable 60-1800 seconds (1 second steps) |
Extinguishant output end-of-line |
“Terminator” circuitry EOL (Part No. EP214) |
|
|
Monitored Inputs |
|
Number of monitored inputs and type : |
6 (Manual Release, Flow Switch, Low Pressure, Mode, Hold, Abort) |
Thresholds : |
8k to 2k ohms (normal); 1.8k to 200 ohms (active), 150 to 0 ohms (short circuit) |
End-Of-Line Resistor Value : |
6K8± 5%, 0.25W |
|
|
Controls & Indicators |
|
Status Display Unit |
128 x 64 pixel graphic LCD unit, two-colour backlight |
|
• Display Faults • Display Disablements • Zones in Test • Lamp Test • Alarm Counter |
LCD ‘Access Level 2’ Menus: |
• Display Faults • Display Disablements • Zones in Test • Lamp Test • Alarm Counter • Set Time/Date • Event Log • Display Contrast • Disablements |
LCD ‘Access Level 3’ Menus: |
• Display Faults • Display Disablements • Zones in Test • Display RSUs • Disablements • Commissioning • Engineering |
Controls (2 x keyswitches) |
• Accessed • Manual Only or Manual & Automatic |
Controls (push buttons) |
• Menu • Silence Internal Sounder •Control Panel Reset • Silence/Resound Sounders • Scroll up • Scroll down • Escape • Accept • Extinguisher Release (housed in yellow casing). |
Indicators (LEDs) |
• General Fire • Fire Zones (x3) • General Disablement • Zone Fault/Disable/Test (x3) • Hold • First Stage Output • Release Imminent (x2) • Extinguishant Released • Abort • Disablements (Extinguishant Release, Manual Release, First Stage Output, Second Stage Output, Sounder) • Manual Only • Manual & Automatic • Supply Present • PSU Fault • Accessed • Test • General Fault • System Fault • Delays • Sounder Fault • Flooding Zone Fault • Low Press Fault. |
Internal control (push button) |
Access Level 3 Switch (located on Main Control PCB) |
|
|
Dimensions (W x H x D) |
|
Dimensions : |
Back box = 439mm x 276mm x 70mm approx. (metal); Lid = 467mm x 293mm x 29mm approx. (plastic) |
Weight : |
4.65kg (without batteries) |