EP203 Automatic Extinguisher Panel

 

The EP203 three zone automatic extinguisher panel has been specifically designed for use in areas housing expensive, dangerous or irreplaceable items of equipment.

Third-party approved by the LPCB to EN 12094-1 (the European standard for Fixed Firefighting Systems - Components for Gas Extinguishing Systems) and EN54 parts 2 and 4, the panel epitomises quality, durability and reliability.

Featuring an intuitive 128 x 64 pixel two-colour graphic display that gives clear and concise feedback to the user, installer and commissioning engineer, the panel also includes six monitored inputs (including hold and abort), a time stamped log, adjustable flood times and volt-free changeover relays for fire, local fire, 1st stage active, 2nd stage active, extractor fan and fault.

The panel is supplied in an elegantly styled, durable enclosure with all of its electronics - apart from its powerful 3A EN54-4 switch mode PSU - mounted on a detachable metal bridge plate for ease of installation. A wide range of ancillaries are also available including remote status units, hold-off and abort buttons, line terminators and output expansion relay boards.


Price : On Request - In Stock.
 
Specifications
Power Supply Specification
Mains Supply Voltage : 220V 50Hz AC
Internal Power Supply : 24V Noninal
Max. Output Current : 3A @230V AC
Power Rating (Including Charging) : 1,5A Cont. , 3A Peak
Battery Type : 2 X 12V 7Ah VRLA Tip Akü (Seri Bağlantı)
Battery Charge Current : 0,7A
Earth Fault Monitoring : YES
Mains Supply / Battery Charged Monitorinf for failure : YES
Batteries Monitored for disconnection or failure : YES
Quiescent Current drain on mains Fail: 40mA
   
Detector Circuit Specification
No. of Conventional Circuits : 3 X 21-28V
Line monitored for open and short circuit : VAR
Max. Cable Lenght Per Circuit : 250 Metre
Max. Number of Smoke/Heat Detector Per Circuit : 20 Adet
Max. Number of Combine Smoke/Call Point Per Circuit : 32 Adet
Zone Quiescent Current : 2mA Max
End-Of-Line Resistor Value : 6K8 ohm ± 5%, 0.25W
   
Sounder Circuit Specification  
No. of Conventional Circuit : 3 (two x 1st stage, one x 2nd stage)
Line monitored for open and short circuit faults : YES
Sounder outputs rating : 21-28Vdc, fused @200mA per circuit
Max. sounder cable length per circuit : Her bir devre için 50 Metre
Max. number of polarised sounders per circuit : 10 @ 20mA each
End-of-line resistor value : 6K8 ohm ± 5%, 0.25W
   
Auxiliary outputs  
No. of auxiliary outputs *: 6 (Fire, Local Fire, Extract Fan, 1st Stage, 2nd Stage, Fault)
Relay contact rating : 30Vdc, 1A maks.
   
Extinguishant release outputs  
Extinguishant release output 21-28Vdc, rated at 1A for 5mins
Extinguishant release time delay Adjustable 0-60 seconds (1 second steps)
Extinguishant release duration Adjustable 1-300 seconds (1 second steps)
Extinguishant release flooding time Adjustable 60-1800 seconds (1 second steps)
Extinguishant output end-of-line “Terminator” circuitry EOL (Part No. EP214)
   
Monitored Inputs  
Number of monitored inputs and type : 6 (Manual Release, Flow Switch, Low Pressure, Mode, Hold, Abort)
Thresholds : 8k to 2k ohms (normal); 1.8k to 200 ohms (active), 150 to 0 ohms (short circuit)
End-Of-Line Resistor Value : 6K8± 5%, 0.25W
   
Controls & Indicators  
Status Display Unit 128 x 64 pixel graphic LCD unit, two-colour backlight
  • Display Faults • Display Disablements • Zones in Test • Lamp Test • Alarm Counter
LCD ‘Access Level 2’ Menus: • Display Faults • Display Disablements • Zones in Test • Lamp Test • Alarm Counter • Set Time/Date • Event Log • Display Contrast • Disablements
LCD ‘Access Level 3’ Menus: • Display Faults • Display Disablements • Zones in Test • Display RSUs • Disablements • Commissioning • Engineering
Controls (2 x keyswitches) • Accessed • Manual Only or Manual & Automatic
Controls (push buttons) • Menu • Silence Internal Sounder •Control Panel Reset • Silence/Resound Sounders • Scroll up • Scroll down • Escape • Accept • Extinguisher Release (housed in yellow casing).
Indicators (LEDs) • General Fire • Fire Zones (x3) • General Disablement • Zone Fault/Disable/Test (x3) • Hold • First Stage Output • Release Imminent (x2) • Extinguishant Released • Abort • Disablements (Extinguishant Release, Manual Release, First Stage Output, Second Stage Output, Sounder) • Manual Only • Manual & Automatic • Supply Present • PSU Fault • Accessed • Test • General Fault • System Fault • Delays • Sounder Fault • Flooding Zone Fault • Low Press Fault.
Internal control (push button) Access Level 3 Switch (located on Main Control PCB)
   
Dimensions (W x H x D)  
Dimensions : Back box = 439mm x 276mm x 70mm approx. (metal); Lid = 467mm x 293mm x 29mm approx. (plastic)
Weight : 4.65kg (without batteries)
 
EP203 Automatic Extinguisher Panel Wiring Diagram
EP203 Söndürme Paneli Diyagramı
 