ECU-4 SigTEL 4 Line Master Fire Telephone Control Panel

ECU-4 SigTEL 4 Line Master Fire Telephone Control Panel

The ECU-4 is an ideal solution for fire telephone systems, disabled refuge emergency communication systems and stadium marshalling applications. It provides full duplex communication between the central operator and up to four handsfree disabled refuge outstations or fire telephone lines.

With the addition of the ECU-8S expansion panel, the total line capacity can be increased to 12 lines. Thanks to its networking capability, up to four control panels can be interconnected, allowing systems of up to 64 lines in total.

Its front door with LCD display and handset makes on-site use and system management easier. The auto-learn feature recognises connected field devices and allows straightforward commissioning. Semi-flush mounting can be achieved using the AFP385 bezel.

General Features

Technical Specifications

Parameter Value
Approvals / Compliance Fully compliant with BS 5839-9 when correctly designed, installed and commissioned.
Supply Voltage 230V 50/60Hz
Current Consumption 500mA
Internal Power Supply 19V-28.5V (27V nominal). 7V maximum battery fault threshold.
Total Output Current 1.5A @ 230Vac
Quiescent Current 100mA (with panel fault buzzer sounding) + 1mA per Type A fire telephone and 3.2mA per Type B disabled refuge outstation.
Maximum Battery Capacity and Type 2 x 12V 7Ah VRLA sealed lead acid batteries
Number of Lines 4 (expandable up to 12 lines total with ECU-8S 8 line expansion panel)
Auxiliary Relays 30V 1A max. Fault Relay
Open Collector Outputs (OP1): active when the ECU panel is ringing; (OP2): active when any disabled WC alarm system is in call condition; (OP3): active when the handset is lifted and returns to normal 2 minutes after the handset is replaced. 24V, 50mA max.
Other Outputs +24V. Typically used to supply power to equipment connected to the ECU's open collector outputs (relays, etc).
Engineering (AL3) Functions Engineer mode and reset buttons (internal).
Indicators 128 x 64 pixel LCD display; Disablement; System fault; PSU fault; General fault; Power on.
Controls Handset; Scroll button; Hold; Call Accept; Function; Directory; Buzzer Mute
Expansion Connections 2 x CAT5 connectors for ECU-8S expansion panel (cables supplied with ECU-8S). The ECU721 network card allows networking with up to 3 additional ECU-4/8 master panels (1 x ECU721 required for each ECU-4/8 panel).
Product Dimensions 410 W x 250 H x 80 D mm (back box); 439 W x 274 H x 7 D mm (door). The handset projects approximately 80 mm from the front.
Enclosure Metal door and enclosure finished in RAL7035 grey.
IP Rating IP20
Weight 3.1kg (excluding batteries)
Maximum Humidity 95%
Operating Temperature -5ºC to +40ºC