ECU-4 SigTEL 4 Line Master Fire Telephone Control Panel
The ECU-4 is an ideal solution for fire telephone systems, disabled refuge emergency communication systems and stadium marshalling applications. It provides full duplex communication between the central operator and up to four handsfree disabled refuge outstations or fire telephone lines.
With the addition of the ECU-8S expansion panel, the total line capacity can be increased to 12 lines. Thanks to its networking capability, up to four control panels can be interconnected, allowing systems of up to 64 lines in total.
Its front door with LCD display and handset makes on-site use and system management easier. The auto-learn feature recognises connected field devices and allows straightforward commissioning. Semi-flush mounting can be achieved using the AFP385 bezel.
General Features
- Ideal for fire telephone systems, disabled refuge emergency communication systems and stadium marshalling applications.
- Provides duplex communication between the central operator and up to four handsfree disabled refuge outstations or fire telephone lines.
- Total line capacity can be increased to 12 lines using the ECU-8S expansion panel.
- Networking capability allows up to four control panels to be linked together for a total system capacity of up to 64 lines.
- Front door complete with LCD display and handset.
- Full duplex speech communication.
- Fast auto-learn feature recognises connected devices and enables easy commissioning.
- Semi-flush mounting is possible using the AFP385 bezel.
- Provides 24 hours standby and 3 hours operation on 2 x 12V 7Ah batteries in the event of mains failure.
- Can interact with NC951 disabled WC alarm kits, PDA induction loop systems, strobes and CCTV trigger relays.
Technical Specifications
| Parameter | Value |
|---|---|
| Approvals / Compliance | Fully compliant with BS 5839-9 when correctly designed, installed and commissioned. |
| Supply Voltage | 230V 50/60Hz |
| Current Consumption | 500mA |
| Internal Power Supply | 19V-28.5V (27V nominal). 7V maximum battery fault threshold. |
| Total Output Current | 1.5A @ 230Vac |
| Quiescent Current | 100mA (with panel fault buzzer sounding) + 1mA per Type A fire telephone and 3.2mA per Type B disabled refuge outstation. |
| Maximum Battery Capacity and Type | 2 x 12V 7Ah VRLA sealed lead acid batteries |
| Number of Lines | 4 (expandable up to 12 lines total with ECU-8S 8 line expansion panel) |
| Auxiliary Relays | 30V 1A max. Fault Relay |
| Open Collector Outputs | (OP1): active when the ECU panel is ringing; (OP2): active when any disabled WC alarm system is in call condition; (OP3): active when the handset is lifted and returns to normal 2 minutes after the handset is replaced. 24V, 50mA max. |
| Other Outputs | +24V. Typically used to supply power to equipment connected to the ECU's open collector outputs (relays, etc). |
| Engineering (AL3) Functions | Engineer mode and reset buttons (internal). |
| Indicators | 128 x 64 pixel LCD display; Disablement; System fault; PSU fault; General fault; Power on. |
| Controls | Handset; Scroll button; Hold; Call Accept; Function; Directory; Buzzer Mute |
| Expansion Connections | 2 x CAT5 connectors for ECU-8S expansion panel (cables supplied with ECU-8S). The ECU721 network card allows networking with up to 3 additional ECU-4/8 master panels (1 x ECU721 required for each ECU-4/8 panel). |
| Product Dimensions | 410 W x 250 H x 80 D mm (back box); 439 W x 274 H x 7 D mm (door). The handset projects approximately 80 mm from the front. |
| Enclosure | Metal door and enclosure finished in RAL7035 grey. |
| IP Rating | IP20 |
| Weight | 3.1kg (excluding batteries) |
| Maximum Humidity | 95% |
| Operating Temperature | -5ºC to +40ºC |
System Architecture and Wiring