ECU-16 SigTEL 16 Line System Controller
The ECU-16 is an ideal solution for fire telephone systems, disabled refuge emergency communication systems and stadium marshalling systems. It allows the central operator to communicate in full duplex mode with up to 16 handsfree disabled refuge outstations or fire telephone lines.
Thanks to its networking capability, up to 14 control panels can be interconnected, providing a total system capacity of up to 224 lines. Its front door with LCD display and handset makes on-site operation and system management much easier.
The auto-learn function quickly recognises connected field devices and allows fast and easy commissioning. Semi-flush mounting can also be achieved using the AFP385 bezel.
General Features
- Ideal for Fire Telephone Systems, Disabled Refuge Emergency Communication Systems and Stadium Marshalling Systems.
- Allows the central operator to communicate in duplex mode with 16 handsfree disabled refuge outstations or fire telephone system lines.
- Can reach a total capacity of up to 224 lines by networking 14 control panels together.
- Front door complete with LCD display and handset.
- Full duplex speech communication.
- Auto-learn function recognises connected equipment for fast and easy commissioning.
- Can be semi-flush mounted using the AFP385 bezel.
- In the event of a mains failure, 2 x 12V 7Ah batteries provide 24 hours standby and 3 hours operation.
- Can interface with NC951 accessible WC alarm kits, PDA induction loop systems, beacons and CCTV trigger relays.
Technical Specifications
| Parameter | Value |
|---|---|
| Approvals / Compliance | Fully compliant with BS 5839-9 when correctly installed, designed and commissioned. |
| Supply Voltage | 230V 50/60Hz |
| Current Consumption | 500mA |
| Internal Power Supply | 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault). |
| Total Output Current | 1.5A @ 230Vac |
| Quiescent Current | 100mA (with the panel fault buzzer sounding) + 1mA per Type A Fire Telephone and 3.2mA per Type B disabled refuge outstation. |
| Maximum Battery Capacity and Type | 2 x 12V 7Ah VRLA sealed lead-acid batteries |
| Number of Lines | 16 (expandable up to a total of 224 lines via additional networked master control panels). |
| Auxiliary Relays | 30V 1A max. fault relay |
| Open Collector Outputs | (OP1): active when the ECU panel is ringing; (OP2): active when any accessible WC alarm system is in call condition; (OP3): active when the handset is lifted and returns to normal 2 minutes after the handset is replaced. 24V, 50mA max. |
| Other Outputs | Generally used to provide +24V supply for devices that can be connected to the ECU panel’s open collector outputs. |
| Engineering (AL3) Functions | Engineering mode and reset button (internal). |
| Indicators | 128 x 64 pixel LCD display; Disablement; System fault; PSU fault; General fault; Power on. |
| Controls | Handset; Scroll buttons; Hold; Call Accept; Function; Directory; Silence Buzzer. |
| Expansion Connections | With ECU721, up to 14 additional ECU-4/8/16 master control panels can be networked together (one ECU721 network card required per panel). |
| Product Dimensions | 410 W x 250 H x 80 D mm (back box); 439 W x 274 H x 7 D mm (door). The handset projects approximately 80 mm from the front cover. |
| Enclosure | Metal lid and enclosure, RAL7035 grey finish |
| IP Rating | IP20 |
| Weight | 3.1kg (excluding batteries) |
| Maximum Humidity | 95% |
| Operating Temperature | -5ºC to +40ºC |
System Architecture and Wiring