Vimpex IS FlashDome - Intrinsically Safe Beacon
The IS FlashDome is an intrinsically safe beacon for use in hazardous areas.
Certified to ATEX and IEC Ex, the IS FlashDome is designed for use in Zones 0, 1 & 2. In order to be intrinsically safe, the IS FlashDome must be powered via an approved 28 V 300 zener barrier or galvanic isolator.
Suitable barriers and isolators are available from Furkan Engineering
![]() |
![]() |
Technical Specification
| Ordering Code : | 8645700 |
|---|---|
| Supply Voltage : | 15 - 28 Vdc |
| Current : | 5 mA (@24 Vdc via a 28 V 300 barrier) |
| Flash Frequency : | 1 Hz (1 flash/second) |
| Interinsic Safe Approval : | EN 60079-0:2004, N60079-26:2004, EN50020:2002* II 1G EEx/Ex ia IIC T4 (-40oC < +70 oC) II 1G EEx/Ex ia IIC T5 (-40oC < +40 oC) ITS06ATEX25407X IEC Ex ITS06. 0018X WEEE Compliant |
| Installation : | Connection must be made via a certified galvanic isolator or zener barrier with output parameters not exceeding Ui=28V, Ii=93mA, Pi=0.66W. The output current of the barrier must be limited by resistor 'R' such that Ii=Ui/R |
| Suitable Zones : | 0,1,2 |
| Operating Temperature : | -40° +70°C |
| Material : | Body - Flame retardant ABS Lens - Polycarbonate |
| IP Rating : | IP66 |
| Weight : | 140gr |