Main Page > Fire Alarm Systems > Extinguisher Panels > EP210F Flush Mount Remote Status Unit |
|
C-TEC EP210F Flush Mount Remote Status Unit |
|
|
- EP210F is designed to connect to the RS485 terminals on an EP203 Automatic Extinguisher Panel to provide remote system status indication via a 128 x 64 pixel LCD status display.
- Also includes a pull-down manual release button, a mode (auto/manual) keyswitch and a wide range of system status indicators.
Three monitored input connections (Hold, Abort and Mode).
Max. 8 remote status units per EP203 panel.
Surface remote status units (EP210S) and weather proof enclosures (BF359/1) also available.
|
|
|
Technical Specification |
EP210F |
Power Requirements : |
21-28VDC (200mA electronic fuse). |
Quiescent Current : |
7mA. |
Auxiliary Inputs : |
Three: (1) Hold; (2) Abort; (3) Mode. A 6k8 EOL resistor must be fitted across the terminals of the last device on each monitored input circuit. Unused circuits must have the 6k8 resistor fitted at the terminals |
Indicators : |
Gen. fire; Fire Zones (x3); Gen. disablement; Hold; 1st Stage Output; 2nd Stage Output; Release Imminent (x2); Exting. Released; Abort; Gen. Fault; Man. Only; Man/Auto. |
Controls : |
Extinguishant release (housed in yellow casing); Operation keyswitch (Manual only or Manual & Auto). |
Dimensions : |
160 W x 240 H x 51 D mm. |
Construction & Finish |
Metal |
IP Rating : |
IP30. |
Weight : |
1.498kg. |
Network Specification : |
RS485; Max. 8 remote status units (any mix) per EP203; Four wire connection (2 power, 2 data); Daisy-chain wiring. |
Working Temperature & Humidity : |
-5ºC +40ºC , 95%. |
|
|
|
|
Other Products We Recommend |
|
Solo 330 -Detector Tester
|
|
|
|
|
|
|
|
|
FURKAN ENGINEERING 2021
|
www.furkanmuhendislik.com.tr | info@furkanmuhendislik.com.tr |