E2S GNExS2 Explosion Proof Alarm Horn Sounder 123dB

E2S GNExS2 Explosion Proof Alarm Horn Sounder 123dB

The flameproof GNExS2 explosion proof alarm sounder is suitable for Zone 1 & Zone 2 applications - certified to ATEX and IECEx.

Sound level ouputs are up to 123dB(A) at 1 metre with a choice of 64 alarm tones and 4 remotely selectable stages. The alarm tone frequencies for the first 2 stages are independently selectable. The GNEx range features enclosures manufactured from GRP (glass reinforced polyester), moulded in natural red, but also available in other colours. 
The re-entrant flare horn is high impact, fire retardant ABS. All models have two M20 cable entries, large termination areas containing in & out terminals and an ingress protection of IP66/67.

General Features

Technical Specification

Ordering Codes :

GNEXS2 DC024B1A1R

Maximum Output : 123dB(A) @ 1 metre [114dB(A) @ 10ft/3m]
Nominal Output : 117dB(A) @ 1m +/- 3dB - Tone 2 [108dB(A) @ 10ft/3m]
Number of Tones : 64 (UKOOA / PFEER compliant)
Number of Stages : 4
Volume Conrol : Max. 117dB(A); Min. 108dB(A) - Tone 44
Effective Range : 200m/656ft @ 1KHz
Voltage DC : 24vdc (10-30vdc), 48vdc (38-60vdc)
Voltage AC : 230vac (100-260vac/dc)
Stage Switching : Negative or positive
Ingress Protection : IP66/67
Enclosure Material : GRP (glass reinforced polyester)
Color : RAL3000 Red (others available on request)
Flare Material : High impact UL94 V0 & 5VA FR ABS (Red)
Cable Entries : Dual M20 ISO
Terminals : 0.5 - 2.5mm² (20-14 AWG)
Enclosure Volume : <2 litres
Line Monitoring : Blocking diode included EOL Min. 500 Ohm 2w, or 3k3 Ohm 0.5w resistor or diode (DC versions) can be fitted
Relative Humidity : 95% - Additional tropicalisation is recommended for applications where both high relative humidity and high ambient temperatures exist
Weight : DC: 3.35kg/7.37Ibs AC: 3.55kg/7.81Ibs
Approval :
  • ATEX certificate: SIRA 13ATEX1139X, EN 60079-0 : 2012, EN 60079-1 : 2007

  • IECEx certificate: IECEx SIR 13.0029X, IEC 60079-0 : 2011 (Ed6), IEC 60079-1 : 2007 (Ed6)

  • TR-CU Ex EAC certificate: RU C-GB.AA71.B.00109

Coding :
  • II 2G Ex d IIC T4 Ta. -60° to +50°C
  • II 2G Ex d IIC T3 Ta. -60° to +70°C
  • II 2G Ex d IIB T6 Ta. -60° to +50°C
  • II 2G Ex d IIB T5 Ta. -60° to +65°C
  • II 2G Ex d IIB T4 Ta. -60° to +70°C
WhatsApp Contact