3MK-FCE2 Intelligent Fire Exit Door Alarm
Advanced Emergency Exit Security with Intelligent Dual-Door Monitoring
An intelligent emergency exit door alarm system designed to monitor fire exit doors, featuring 12V DC and 24V DC operation, two independent magnetic contact inputs, selectable alarm durations and advanced user-configurable security functions.
Intelligent Protection for Fire and Emergency Exit Doors
Fire and emergency exit doors must remain accessible for safe evacuation during emergencies. However, unauthorized or uncontrolled use of these doors during normal building operations can create significant security concerns in schools, hospitals, factories, warehouses, shopping centres, residential facilities and commercial buildings.
The 3MK-FCE2 Intelligent Fire Exit Door Alarm provides an effective solution for monitoring emergency exit doors without interfering with their intended evacuation function. The device detects door opening through external magnetic contacts and generates an audible alarm to notify nearby personnel of unexpected or unauthorized door use.
Secure Key-Switch Operation for Authorized Personnel
The integrated mechanical key-switch enables authorized personnel to temporarily deactivate the alarm when controlled access is required for maintenance, cleaning, servicing, equipment movement or other legitimate activities.
Once the activity is completed, the alarm can be rearmed using the same key-switch. An integrated audible reminder function helps prevent the system from being unintentionally left disarmed.
Flexible Monitoring with Advanced Alarm Functions
Unlike conventional single-door alarm devices, the 3MK-FCE2 features two independent magnetic contact inputs, allowing both leaves of a double-leaf emergency exit door or two separate nearby doors to be monitored using a single alarm unit.
Additional intelligent functions include selectable alarm durations, Door Chime operation, automatic rearming reminders, enclosure tamper protection and DIP switch configuration. These features allow the same device to be adapted to different building layouts and operational requirements.
Key Features & Benefits
Two Independent Door Inputs
REED 1 and REED 2 inputs allow two separate magnetic contacts to be monitored by one device. Ideal for double-leaf fire exit doors or two nearby emergency exit doors.
Selectable Alarm Duration
Choose between 30-second, 180-second or continuous audible alarm operation according to the security requirements of the installation.
Automatic Rearming Reminder
If the alarm is deactivated using the key-switch and is not subsequently rearmed, the device provides an audible reminder consisting of two short beeps.
Door Chime Function
When Door Chime mode is enabled, the device generates three short beeps when a connected door opens, even when the main alarm is not armed.
Integrated Tamper Protection
Unauthorized opening of the device enclosure is detected by the integrated tamper protection mechanism, activating the alarm to indicate possible interference with the unit.
DIP Switch Configuration
Alarm duration, Door Chime and relevant operating options can be configured directly through the internal DIP switches without a computer, software or external programming equipment.
12V DC / 24V DC Operation
Compatible with both 12V DC and 24V DC power supplies, supporting installation in a variety of security, fire alarm and building automation environments.
Authorized Key-Switch Control
The mechanical key-switch enables authorized personnel to arm or disarm the alarm during controlled access, maintenance and servicing.
Dual-Door Monitoring with Two Magnetic Contact Inputs
The 3MK-FCE2 incorporates two independent magnetic contact inputs identified as REED 1 and REED 2.
Each input can be connected to a separate external magnetic door contact, enabling the alarm system to monitor two individual door-opening points.
Double-Leaf Emergency Exit Doors
Double-leaf fire exit doors are frequently installed in commercial, industrial and public buildings. These doors consist of two independently opening leaves.
By installing one magnetic contact on each door leaf, the 3MK-FCE2 can detect the opening of either leaf through its separate REED inputs.
Two Separate Emergency Exit Doors
The same dual-input arrangement can be used to monitor two separate emergency exit doors located close to each other, reducing the need for an individual alarm device at every monitored opening.
Application Example: A corridor contains two emergency exit doors positioned near each other. One magnetic contact is installed on each door and connected to REED 1 and REED 2 respectively. When either door is opened while the alarm is armed, the 3MK-FCE2 activates its audible alarm function.
Three Selectable Alarm Duration Modes
Different facilities may require different alarm operating periods. The 3MK-FCE2 offers three selectable alarm duration modes, allowing installers to configure the device according to the specific application.
The selectable alarm duration makes the 3MK-FCE2 suitable for different operating environments, including schools, hospitals, factories, warehouses, residential facilities and commercial buildings.
Automatic Alarm Rearming Reminder
One of the common operational risks associated with emergency exit door alarm systems is the possibility of an alarm being temporarily disabled and then unintentionally left disarmed.
This may occur during maintenance, cleaning, equipment deliveries or other activities requiring controlled access through an emergency exit.
The 3MK-FCE2 incorporates a dedicated audible reminder function to help reduce this risk.
If the alarm has been deactivated through the key-switch and has not been rearmed, the device provides two short beeps to remind personnel that the alarm system should be reactivated.
Operational Benefit: The audible rearming reminder helps prevent accidental long-term deactivation of the emergency exit door monitoring system following authorized use.
Door Chime Function – Audible Door Opening Notification
In addition to emergency exit door security, the 3MK-FCE2 can also operate as a door-opening notification device through its integrated Door Chime function.
When Door Chime is enabled using the internal DIP switch, opening a door connected to either REED 1 or REED 2 causes the device to generate three short beeps.
This notification can operate even when the main alarm is not armed through the key-switch.
Unlike continuous security alarm operation, Door Chime provides a short audible indication intended to notify nearby personnel that a monitored door has been opened.
Retail Application: When installed at the entrance of a shop, showroom or retail business, the 3MK-FCE2 can provide three short beeps whenever the entrance door opens, notifying staff that someone has entered the premises.
This additional functionality extends the potential applications of the device to reception areas, offices, warehouses, retail entrances and other locations requiring audible door-opening notifications.
Integrated Enclosure Tamper Protection
Effective door security requires protection not only against unauthorized door opening but also against interference with the alarm equipment itself.
The 3MK-FCE2 includes integrated enclosure tamper protection designed to detect unauthorized opening of the alarm unit's cover.
When the device enclosure is opened without authorization, the tamper mechanism detects the event and activates the alarm.
This provides an additional layer of protection against attempts to access or interfere with the internal alarm components and connections.
Simple On-Site Configuration with DIP Switches
The operating options of the 3MK-FCE2 can be configured directly on the device using its integrated DIP switch arrangement.
This allows installers and maintenance personnel to adapt the alarm to different site requirements without using a computer, dedicated programming software or external configuration equipment.
Configurable options include alarm duration, Door Chime operation and the relevant user operating functions.
The DIP switch configuration provides a practical approach for installation, commissioning and future adjustment of the alarm system.
Authorized Alarm Control with Mechanical Key-Switch
Emergency exit doors may occasionally need to be opened for authorized activities such as maintenance, cleaning, servicing, equipment movement or emergency evacuation drills.
The 3MK-FCE2 incorporates a mechanical key-switch that enables authorized users to temporarily deactivate and subsequently reactivate the alarm function.
How the Key-Switch Control Works
- Temporary Deactivation: Before controlled door use, authorized personnel deactivate the alarm using the key-switch.
- Authorized Door Operation: The door can be used for maintenance, servicing or other permitted activities.
- Alarm Reactivation: Once the activity is completed, the authorized user rearms the system using the key-switch.
- Rearming Reminder: If the alarm is unintentionally left disarmed, the device provides an audible reminder consisting of two short beeps.
Important: The key-switch controls the alarm function. The emergency exit door must remain available for evacuation in accordance with the applicable fire and building safety requirements.
12V DC and 24V DC Power Supply Compatibility
One of the key advantages of the 3MK-FCE2 is its ability to operate with either 12V DC or 24V DC power supplies.
This dual-voltage compatibility allows the same alarm model to be used in a variety of security and building infrastructure applications.
The device can be incorporated into 12V DC security and access control environments as well as installations using 24V DC power supplies, commonly associated with fire alarm and building automation systems.
Supporting both voltage levels simplifies product selection, system design, inventory management, installation and maintenance.
Integration with External Security and Alarm Systems
The 3MK-FCE2 can operate as an independent emergency exit door alarm or be integrated with compatible external systems through its dry-contact output.
This enables door alarm information to be communicated to other security or building monitoring equipment where appropriate system interfaces are available.
Potential Integration Applications
- Fire alarm systems
- Intruder alarm systems
- Access control systems
- Building automation systems
- Centralized security monitoring systems
- Compatible external audible warning devices
The use of dry-contact signalling provides flexibility when integrating the alarm into existing security infrastructure.
External connections should be designed according to the electrical requirements and compatibility of the connected equipment.
How the 3MK-FCE2 Intelligent Fire Exit Door Alarm Works
1. Armed Standby Mode
When the alarm is armed using the key-switch, the device monitors the connected magnetic contacts through REED 1 and REED 2.
2. Door Opening Detection
When either monitored door or door leaf is opened, the corresponding magnetic contact changes state and the device detects the opening event.
3. Audible Alarm Activation
The alarm activates according to the selected operating mode: 30 seconds, 180 seconds or continuous operation.
4. Automatic Alarm Cycle Completion
In the 30-second and 180-second modes, the audible alarm stops automatically after the configured duration.
When the door closes and is subsequently opened again, a new alarm cycle is initiated.
5. Continuous Alarm Operation
In continuous alarm mode, the audible warning remains active until an authorized user deactivates the alarm through the mechanical key-switch.
6. Authorized Alarm Bypass
Authorized personnel may temporarily disarm the alarm when controlled door access is necessary.
7. Automatic Rearming Reminder
If the alarm is not rearmed after authorized use, the device generates two short beeps as a reminder.
8. Door Chime Operation
When Door Chime is enabled, opening a monitored door produces three short beeps even when the main alarm is not armed.
9. Tamper Detection
Unauthorized opening of the device enclosure is detected by the tamper protection mechanism and activates the alarm.
Technical Advantages of the 3MK-FCE2
-
Dual Magnetic Contact Monitoring
Two independent REED inputs provide flexible monitoring for double-leaf doors or two nearby emergency exits using one alarm device.
-
Three Selectable Alarm Durations
The alarm can be configured for 30-second, 180-second or continuous operation according to site requirements.
-
Intelligent Rearming Reminder
An audible reminder helps prevent the system from remaining unintentionally disarmed after authorized access.
-
Integrated Door Chime
Three short beeps provide a practical door-opening notification for shops, offices, reception areas and other monitored entrances.
-
Enclosure Tamper Protection
The device detects unauthorized opening of its cover and activates an audible alarm.
-
Dual-Voltage Compatibility
Operation with both 12V DC and 24V DC power supplies supports a wide range of installation environments.
-
Direct DIP Switch Programming
Operating functions can be configured directly on the device without additional programming equipment.
-
External System Integration
Dry-contact output functionality supports integration with compatible alarm and security systems.
-
Surface-Mount Installation
The surface-mounted design is suitable for emergency exit door monitoring applications in new and existing buildings.
Typical Applications
The 3MK-FCE2 Intelligent Fire Exit Door Alarm is suitable for a wide range of commercial, industrial, institutional and residential building applications.
- Schools and Educational Facilities: Helps detect unauthorized or uncontrolled use of emergency exit doors during normal school operations.
- Student Dormitories: Provides local audible notification when monitored emergency exits are opened unexpectedly.
- Hospitals and Healthcare Facilities: Helps personnel identify unexpected opening of monitored emergency exit doors.
- Nursing Homes and Care Facilities: Provides an audible warning when monitored exit doors are opened.
- Factories and Manufacturing Plants: Helps monitor emergency exits that may otherwise be used as ordinary personnel access routes.
- Warehouses and Logistics Centres: Supports monitoring of emergency exit doors and identification of unexpected door opening.
- Shopping Centres and Commercial Buildings: Provides local audible alarm functionality and potential integration with central security monitoring equipment.
- Hotels and Accommodation Facilities: Helps detect the unexpected use of monitored fire exit doors during normal operations.
- Retail Stores and Shops: Door Chime mode can provide three short beeps when an entrance door opens.
- Offices and Showrooms: Can be used for controlled door monitoring and audible door-opening notification.
3MK-FCE2 Technical Overview
Technical Specifications
| Specification | Description / Value |
|---|---|
| Model | 3MK-FCE2 |
| Product Description | Intelligent Fire Exit Door Alarm |
| Supply Voltage | 12V DC / 24V DC |
| Number of Door Inputs | 2 independent inputs – REED 1 / REED 2 |
| Door Detection Method | External magnetic door contacts |
| Supported Door Configurations | Single door, double-leaf door or two separate nearby doors |
| Selectable Alarm Duration | 30 seconds / 180 seconds / Continuous |
| 30-Second Alarm Mode | 30-second audible alarm; a new cycle starts when the door is closed and reopened |
| 180-Second Alarm Mode | 180-second audible alarm; a new cycle starts when the door is closed and reopened |
| Continuous Alarm Mode | Alarm continues until deactivated using the key-switch |
| Alarm Rearming Reminder | Two short audible beeps |
| Door Chime Function | Available – three short beeps when a monitored door opens |
| Door Chime Operating Condition | Door-opening notification is available even when the main alarm is not armed |
| Tamper Protection | Integrated enclosure tamper detection; alarm activates when the cover is opened |
| Authorized User Control | Mechanical key-switch |
| Configuration Method | Internal DIP switches |
| External System Integration | Dry-contact output for compatible alarm and security systems |
| Mounting Method | Surface mounting |
| Colour | White |
Ordering Information
| Model Number | Product Description |
|---|---|
| 3MK-FCE2 | Intelligent Fire Exit Door Alarm |
Installation and System Design Considerations
The 3MK-FCE2 is designed for surface-mounted installation in emergency exit door monitoring applications.
External magnetic contacts should be installed on the relevant door or door leaves and connected to the appropriate REED inputs.
The alarm duration and Door Chime functions should be configured according to the operating requirements of the facility.
Where external system integration is required, the dry-contact interface should be connected to compatible equipment according to the relevant installation documentation.
Fire Safety Consideration: The 3MK-FCE2 is an audible door monitoring and alarm device. It must not be used to obstruct, lock or delay emergency evacuation. Emergency exit doors must remain compliant with applicable fire safety and evacuation regulations.