  • • Ideal for disabled refuge, fire telephone and stadium marshalling applications.
  • • Allows operators to communicate with up to four disabled refuge or fire telephone outstations.
  • • Expandable to 16 lines using an ECU-8 expansion unit.
  • • Networking facility allows up to four controllers (plus any expansion units) to be interlinked allowing systems of up to 64 lines to be implemented.
  • • Supplied with a backlit LCD and handset.
  • • True duplex speech.
  • • Unique ‘auto-learn’ facility allows fast system set up.
  • • Can be semi-flush mounted using an AFP385 bezel.
  • • Operation can be maintained for 24 hours (standby) and 3 hours (in use) using 2 x 12V 7 Ahr batteries.
  • • Easily interfaced to NC951 accessible toilet alarms, PDA audio-frequency induction loop systems, strobes, CCTV activation relays, etc.

Price : On Request
 
Technical Specification
Approval / Certifications : Facilitates compliance with BS5839-9 when correctly installed.
Mains Supply : 230V 50/60Hz.
Mains Rated Current : 500mA.
Internal Power Supply : 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
Total Output Current Limited To :

1.5A @ 230Vac

Quiscent Current : 100mA (controller with fault buzzer sounding) plus 1mA per Type A outstation and 3.2mA per Type B outstation.
Maximum Battery Size and Type : 2 x 12V 7Ah VRLA connected in series.
Number of Lines : 8 (expandable to 16 via an ECU-8S 8 line expansion unit).
Auxillary Relays : Changeover fault relay (failsafe). 30V 1A max.
Open Collector Outputs : (OP1): Activates when the ECU is ringing; (OP2) Activates when there is an active accessible toilet alarm call; (OP3) Closes when the handset is off hook and remains active for 2 mins after it is replaced. 24V, 50mA max.
Other Outputs : +24 V. Typically used to supply power to equipment connected to the ECU's open collector outputs (relays, etc).
Engineering (AL3) Functions : Engineer mode and reset buttons (internal).
Indicators : 128 x 64 pixel LCD display; Disablement; System fault; PSU fault; General fault; Power on.
Controls : Handset; Scroll buttons; Hold; Call Accept; Function; Directory; Silence Buzzer.
Expansion Connection : 2 x CAT5 connectors provided for an optional ECU-8S expansion unit (leads supplied with ECU-8S). ECU721 network card allows the connection of up to 3 additional ECU-4/8 controllers (1 x ECU721 per ECU-4/8).
Product Dimensions : 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid). Handset protrudes 80 mm beyond lid.
Construction and Finish Metal lid and base, RAL7035 grey texture.
IP Rating : IP20.
Weight : 3.1kg (without batteries).
Operating Temperature : -5ºC to +40ºC. Max relative humidity: 95%.
 
System Architecture Diagram & Cabling

 
 
Other Products We Recommend

Solo 330 -Detector Tester
Price:On-Request
Solo A4 - Smoke Aerosol
Price:On-Request
Solo C3 -CO Aerosol
Price:On-Request
 

 
  • Design and specifications are subject to change without prior notice.
 
Bookmark and Share
FURKAN ENGINEERING 2019
www.furkanmuhendislik.com.tr | info@furkanmuhendislik.com.tr