Approval / Certifications : |
Facilitates compliance with BS5839-9 when correctly installed. |
Mains Supply : |
230V 50/60Hz. |
Mains Rated Current : |
500mA. |
Internal Power Supply : |
19V-28.5V (27V nominal). Ripple 7V maximum (battery fault). |
Total Output Current Limited To : |
1.5A @ 230Vac |
Quiscent Current : |
100mA (controller with fault buzzer sounding) plus 1mA per Type A outstation and 3.2mA per Type B outstation. |
Maximum Battery Size and Type : |
2 x 12V 7Ah VRLA connected in series. |
Number of Lines : |
4 (expandable to 12 via an ECU-8S 8 line expansion unit). |
Auxillary Relays : |
Changeover fault relay (failsafe). 30V 1A max. |
Open Collector Outputs : |
(OP1): Activates when the ECU is ringing; (OP2) Activates when there is an active accessible toilet alarm call; (OP3) Closes when the handset is off hook and remains active for 2 mins after it is replaced. 24V, 50mA max. |
Other Outputs : |
+24 V. Typically used to supply power to equipment connected to the ECU's open collector outputs (relays, etc). |
Engineering (AL3) Functions : |
Engineer mode and reset buttons (internal). |
Indicators : |
128 x 64 pixel LCD display; Disablement; System fault; PSU fault; General fault; Power on. |
Controls : |
Handset; Scroll buttons; Hold; Call Accept; Function; Directory; Silence Buzzer. |
Expansion Connection : |
2 x CAT5 connectors provided for an optional ECU-8S expansion unit (leads supplied with ECU-8S). ECU721 network card allows the connection of up to 3 additional ECU-4/8 controllers (1 x ECU721 per ECU-4/8). |
Product Dimensions : |
410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid). Handset protrudes 80 mm beyond lid. |
Construction and Finish |
Metal lid and base, RAL7035 grey texture. |
IP Rating : |
IP20. |
Weight : |
3.1kg (without batteries). |
Operating Temperature : |
-5ºC to +40ºC. Max relative humidity: 95%. |