English
About us | Jobs | +90 212 483 17 83 | Contact

 
Main Page > Fire and Gas Alarm Systems > Conventional Fire Alarm Control Panels > CFP-704 C-TEC 4 Zone Fire Alarm Control Panel

 

C-TEC CFP-704E 4 Zone Fire Alarm Control Panel

Fire Alarm Control Panels

CFP-702 Fire Alarm Control Panel


 

CFP704 CFP Standard 4 Zone Panel - Fully compliant with EN54 parts 2 and 4, C-TEC's CFP conventional fire alarm panel offers an array of user and installer friendly features. Supplied in an attractive flush or surface mountable plastic enclosure, each featuring four conventional sounder circuits, glass change and alert inputs, two fire outputs, a fault output and a reset output.
LPCB EN54 Europen Norm British Fire Assocition


Technical Specification

Power Supply
C-TEC CFP-702
Supply Voltage (VAC)
230V 50/60Hz
Current
350mA maximum
Internal Supply Voltage
19V - 28.5V (27V nominal). Ripple 7V maximum (battery fault)
Total Output Current
1.5A @ 230Vac (ImaxA = 146mA)
Battery Cut Out Monitoring
YES
Battery Fault Monitoring
YES
Battery Discharge Monitoring
YES (Below 21V)
Maximum Battery Size
2 x 3,3Ah
Main fuse
240V 1A HRC ceramic 20mm compliant with IEC (EN60127 PT2)
Battery Fuse
1.6A F 20mm compliant with IEC (EN60127 PT2)
Detector Circuit
 
Zone
4
Maximum Zone Cable Lenght
500 meter
Cable Type
1mm2
Connector
1.5mm2
Short Circuit and Open Circuit Monitoring
YES
Maximum Cable Impedance
20 Ohm
Maximum Cable Capacity
0.27uF
Alarm Resistance
470 - 680Ohm
Maximum Detector Number per Zone
25 Adet
Maximum Detector and Call Point Number per Zone
32 Adet
Sounder Circuit
 
Sounder Output
4
Maximum Cable Lenght
500 Meter
Cable Type
1mm2
Connektor
1.5mm2
Sounder EOL (End of Line)
6800 ohm 5% Tol. 0.25W (mavi,gri,kırmızı,altın)
Sounder Output Voltage
27V maximum , 20V minimum
Sounder Output Fuses
Electonic Resettable
Maximum Output Current
4 x 200mA = 800mA
Phisical
 
Dimensions
380mm x 235mm x 96mm
Weight
1.75kg
 
 
Bookmark and Share
FURKAN ENGINEERING 2012
www.furkanmuhendislik.com.tr | info@furkanmuhendislik.com.tr